The set up of the robot controller has to be done after receiving the components.
+
<span style="color:#008000">'''If you have ordered the ''robot including controller'' directly from CPR, the robot and its control electronics have been configured and tested. The following procedure described on this page does not need to be carried out.'''</span>
 
 
  
 +
<span style="color:#800000">'''If you have ordered the control electronics ''separately'', it needs to be set up and configured to correctly control the joints of a robot.'''</span>
 +
== Robot and controller configured by CPR ==
  
----
+
The procedure to commission the robot is shown below.
  
== Robot and controller configured by CPR ==
+
[[file:caution.png|frameless|50px]] '''Do not hot-plug! Always switch of the power supply and wait a few seconds before working on the connectors! Failing to do so can cause damage to the electronics modules'''
 +
<br clear=all>
  
When you ordered robot and controller by CPR, then the cables are already equipped with the according plugs and the robot has been configured and tested. The procedure to run the robot is shown below.
+
In some cases screws in the joints 2, 3 or 4 have been removed to decrease packaging size. Re-assemble the robot with these screws.
  
''Attention: Do not hot-plug! Always switch of the power supply and wait a few seconds before working on the connectors!''
+
===Set up and check the controller:===
  
* In some cases screws in the joints 2, 3 or 4 have been removed to decrease packaging size. Re-assemble the robot with these screws.
+
* Connect/check that the emergency stop button is plugged into the E-Stop connector on the Support module
* Set up the controller:
+
* Connect/check that the closed loop connector is plugged into the Ext-Relay connector on the Support module
** Connect/check that the emergency stop button is plugged into the E-Stop connector on the Support module
+
* Connect/check that the [https://www.peak-system.com/PCAN-USB.199.0.html PCAN-USB adapter] is connected with the according cable to the CAN connector on the Support module   
** Connect/check that the closed loop connector is plugged into the Ext-Relay connector on the Support module
 
** Connect/check that the PCAN-USB adapter is connected with the according cable to the CAN connector on the Support module   
 
 
* Provide 24V power supply
 
* Provide 24V power supply
 
** If the controller has been delivered with power supply just connect it to the 110/220V plug
 
** If the controller has been delivered with power supply just connect it to the 110/220V plug
** If you use an existing power supply connect this to the control using the fuse. The supply should provide at least 5A at 24V
+
** If you use an existing power supply, connect it to the control via the fuse. The supply should provide at least 5A at 24V
  
 
Now the green LEDs on the modules should be on.   
 
Now the green LEDs on the modules should be on.   
Line 26: Line 26:
 
* Press the "Connect" button. Now the green LEDs on the stepper and DIO modules should blink to show activity on the CAN bus
 
* Press the "Connect" button. Now the green LEDs on the stepper and DIO modules should blink to show activity on the CAN bus
  
Switch the robot control off again.
+
===Connect the Joint Cables===
 +
Switch off the robot control electronics.
  
* Connect the joint cables into the stepper modules. The connectors have the joint numbers written on it, and also the function.
+
* Connect the joint cables to the stepper modules. The are labelled with the joint numbers, and also the function.
* Pay attention to add measures to prevent the connectors being pulled out by stress on the cables
+
* Ensure that the connectors cannot be pulled out during robot operation by stress on the cables as hot-plugging the 'Motor' connectors during operation can damage the stepper motor control electronics.
* Switch the power supply on again
+
* Switch on the power supply
* Start CPRog and press "Connect" and "Reset". Now the status on the left changes to "Motors not enabled"
+
* Start CPRog and press "Connect" and "Reset". Now the status in the left column should change to "Motors not enabled"
 
* Release the Emergency Stop and press "Enable". Now the status on the left changes to "No Error"
 
* Release the Emergency Stop and press "Enable". Now the status on the left changes to "No Error"
 
* Now you can jog the robot arm
 
* Now you can jog the robot arm
 
* Proceed with referencing the robot ([[Referencing robolink]]) and programming the arm
 
* Proceed with referencing the robot ([[Referencing robolink]]) and programming the arm
  
 +
== Configure the control electronics for your robot ==
 +
<span id="Swap encoder direction"></span>
 +
 +
If the robot with electronics has '''not''' been configured by CPR because the robot was bought separately from the control electronics, then the following steps have to be performed:
 +
 +
===Prepare the Cables===
 +
* Add the connectors provided by CPR to the motor, encoder and reference cables. This is shown in the [http://www.cpr-robots.com/download/CPRog/UserGuide_igusRobolink.pdf robolink User Guide].
 +
 +
===Test single Joints===
 +
* Set up the robot control and CPRog as described above
 +
* Now every single joint should be tested using the ModuleCtrl software
 +
** [[file:caution.png|frameless|50px]]'''Again, avoid hot-plugging, i.e. never connect or disconnect anything while mains power is connected.'''
 +
** Install the ModuleCtrl software: [[Config Software ModuleCtrl]].
 +
** Connect the cables for one joint with the according stepper module
 +
** Start ModuleCtrl, choose the correct CAN-ID: 0x10 for Joint1, 0x20 for Joint2, ... and press "Connect"
 +
** Press "SetToZero", "Reset" and "Enable". Now you should be able to move the joint with the center dial.
  
 +
===Invert the Encoder Direction for Joint5===
 +
[[file:ModuleCtrl-swap-encoder-direction.png|thumb|300px|left|Swap Encoder Direction]]
 +
The Joint5 encoder is mounted in opposite direction then the other encoders in some robot models. When testing this results in an increasing motion of the joint 5 until the position lag error stops the operation. The stepper module has to be configured accordingly:
 +
* Change to tab "Stepper" and click on "Read from Board".
 +
* Toggle the "Swap encoder direction" box.  Changing this parameter takes effect only after a cold-start of the contorl electronics.
 +
* Save the parameters to the board: Click on "Write to Board" in the bottom right corner of the window.
 +
* Switch off the control electronics and close the ModuleCtrl Software, wait a few seconds and switch on the control electronics.
 +
<br clear=all>
 +
====To verify the correct operation of the encoder direction of joint 5====
 +
[[file:ModuleCtrl-positionMode.png|thumb|left|300px|When testing the encoder direction, e.g. of joint 5, ModuleCtrl needs to be in "Position" mode.]]
 +
* start the robot, and the ModuleCtrl software
 +
* select CAN ID 0x50 and click "Connect", "Reset" and "Enable"
 +
* Ensure that ModuleCtrl is in "Position" mode, so that the encoder information is used. In "Velocity" mode, the encoder info is disregarded, hence you would not be able to find out whether the correct encoder direction has been chosen.
 +
* Zero the current encoder position by clicking on "Zero Position".
 +
* Move the big dial in the middle of the window a small amount. joint 5 should move to the new position. Once the motor has stopped moving, you should see that the values in the fields "Position SetPoint" and "Current Position" are identical.
  
----
+
<br clear=all>
== Configure Robot for Controller ==
 
  
If the robot has not been configured by CPR then the following additional steps have to be performed:
+
===If the cables of the robot are not marked===
 +
In some cases the cables might not be marked, then it is difficult to find the right cables for each joint. Some hints:
 +
* Connect 3 cables to the joint 1 module
 +
* Start the control and the ModuleCtrl software, connect to the right joint
 +
* Rotate all robot joints a little bit with your hand. You will see a motion in the range of some tics on the right display when you move the one that is connected.
 +
* Place a screw drivers head or another piece of metal before the reference switches. The connected one will light up.
 +
* When enabling the motor the joint will probably speed up into one direction due to the missing encoder signals, so place your hand on the emergency stop button.
 +
* This way it should be possible with some trial and error to find the right combination of motor, encoder and reference cables.
  
* Add the connectors to the cables. This is shown in the user guide.
 
* Test the single joints:
 
*
 
 
   
 
   
  
Line 53: Line 88:
 
----
 
----
  
For questions or comments please get in contact with us: info(at)cpr-robots.com
+
For questions or comments please [[Support Routes|get in contact with us]].
 +
[[Category:ModuleCtrl]]

Latest revision as of 10:04, 16 August 2023

If you have ordered the robot including controller directly from CPR, the robot and its control electronics have been configured and tested. The following procedure described on this page does not need to be carried out.

If you have ordered the control electronics separately, it needs to be set up and configured to correctly control the joints of a robot.

Robot and controller configured by CPR

The procedure to commission the robot is shown below.

Caution.png Do not hot-plug! Always switch of the power supply and wait a few seconds before working on the connectors! Failing to do so can cause damage to the electronics modules

In some cases screws in the joints 2, 3 or 4 have been removed to decrease packaging size. Re-assemble the robot with these screws.

Set up and check the controller:

  • Connect/check that the emergency stop button is plugged into the E-Stop connector on the Support module
  • Connect/check that the closed loop connector is plugged into the Ext-Relay connector on the Support module
  • Connect/check that the PCAN-USB adapter is connected with the according cable to the CAN connector on the Support module
  • Provide 24V power supply
    • If the controller has been delivered with power supply just connect it to the 110/220V plug
    • If you use an existing power supply, connect it to the control via the fuse. The supply should provide at least 5A at 24V

Now the green LEDs on the modules should be on.

  • Install and start CPRog from the provided CD
  • Load the correct project using the "Load Project" Button in the menu on the upper-left circle
  • Press the "Connect" button. Now the green LEDs on the stepper and DIO modules should blink to show activity on the CAN bus

Connect the Joint Cables

Switch off the robot control electronics.

  • Connect the joint cables to the stepper modules. The are labelled with the joint numbers, and also the function.
  • Ensure that the connectors cannot be pulled out during robot operation by stress on the cables as hot-plugging the 'Motor' connectors during operation can damage the stepper motor control electronics.
  • Switch on the power supply
  • Start CPRog and press "Connect" and "Reset". Now the status in the left column should change to "Motors not enabled"
  • Release the Emergency Stop and press "Enable". Now the status on the left changes to "No Error"
  • Now you can jog the robot arm
  • Proceed with referencing the robot (Referencing robolink) and programming the arm

Configure the control electronics for your robot

If the robot with electronics has not been configured by CPR because the robot was bought separately from the control electronics, then the following steps have to be performed:

Prepare the Cables

  • Add the connectors provided by CPR to the motor, encoder and reference cables. This is shown in the robolink User Guide.

Test single Joints

  • Set up the robot control and CPRog as described above
  • Now every single joint should be tested using the ModuleCtrl software
    • Caution.pngAgain, avoid hot-plugging, i.e. never connect or disconnect anything while mains power is connected.
    • Install the ModuleCtrl software: Config Software ModuleCtrl.
    • Connect the cables for one joint with the according stepper module
    • Start ModuleCtrl, choose the correct CAN-ID: 0x10 for Joint1, 0x20 for Joint2, ... and press "Connect"
    • Press "SetToZero", "Reset" and "Enable". Now you should be able to move the joint with the center dial.

Invert the Encoder Direction for Joint5

Swap Encoder Direction

The Joint5 encoder is mounted in opposite direction then the other encoders in some robot models. When testing this results in an increasing motion of the joint 5 until the position lag error stops the operation. The stepper module has to be configured accordingly:

  • Change to tab "Stepper" and click on "Read from Board".
  • Toggle the "Swap encoder direction" box. Changing this parameter takes effect only after a cold-start of the contorl electronics.
  • Save the parameters to the board: Click on "Write to Board" in the bottom right corner of the window.
  • Switch off the control electronics and close the ModuleCtrl Software, wait a few seconds and switch on the control electronics.


To verify the correct operation of the encoder direction of joint 5

When testing the encoder direction, e.g. of joint 5, ModuleCtrl needs to be in "Position" mode.
  • start the robot, and the ModuleCtrl software
  • select CAN ID 0x50 and click "Connect", "Reset" and "Enable"
  • Ensure that ModuleCtrl is in "Position" mode, so that the encoder information is used. In "Velocity" mode, the encoder info is disregarded, hence you would not be able to find out whether the correct encoder direction has been chosen.
  • Zero the current encoder position by clicking on "Zero Position".
  • Move the big dial in the middle of the window a small amount. joint 5 should move to the new position. Once the motor has stopped moving, you should see that the values in the fields "Position SetPoint" and "Current Position" are identical.


If the cables of the robot are not marked

In some cases the cables might not be marked, then it is difficult to find the right cables for each joint. Some hints:

  • Connect 3 cables to the joint 1 module
  • Start the control and the ModuleCtrl software, connect to the right joint
  • Rotate all robot joints a little bit with your hand. You will see a motion in the range of some tics on the right display when you move the one that is connected.
  • Place a screw drivers head or another piece of metal before the reference switches. The connected one will light up.
  • When enabling the motor the joint will probably speed up into one direction due to the missing encoder signals, so place your hand on the emergency stop button.
  • This way it should be possible with some trial and error to find the right combination of motor, encoder and reference cables.





For questions or comments please get in contact with us.